Temp-Tracker Controllers

The Temp Tracker 2- and 4-stage controllers are designed to sequence multiple units, up to 4 total stages, whether it's one to four on/off boilers, two 2-stage boilers, or one boiler with up to four stages. It is available factory-mounted or loose on Hi Delta models, loose for Delta Limited models, and available loose on staged Raytherm models. This control can be used for space heating and hot water supply with 8 applications-specific modes to meet various applications, including outdoor reset for heating applications. It monitors and displays inlet and outlet temperatures on all applications as well as monitoring outdoor ait temperature when an outdoor reset application is utilized.

Temp-Tracker Staged Digital Controllers

Basic Data
Model # of Stages Outdoor Reset Active
B-21 4 no
B-23 4 yes
B-26 2 no
B-27 2 yes
B-28 1 no

*Available for the following units:
Firing Modes Raytherm Sizes Hi Delta Sizes
H3, WH3 181-4001 HD101-HD401, 302B-902B, 399B-899B
H4, WH1 181-4001
H8, WH8   992B-2342B, 989B-2339B
H9, WH9 514-4001 1262B-2342B, 1259B-2339B

B-28 controller available loose, and mounted on Hi Deltas only.
Features:
  • Up to 4 stages of control depending on model
  • Basic lead/lag function
  • LCD display
  • P or PID control algorithm
  • Boiler inlet and boiler outlet water sensors included
  • System water sensor included
  • Outdoor air sensor included (B-23 and B-27 only)
  • Low power consumption: 24VAC 60 Hz, 3 VA
 

Temp-Tracker Mod+ Hybrid Controller

With the introduction of the MVB product line, Raypak offered a robust controller to support multiple boilers or multiple water heaters without sacrificing any of the reliability for which we are known. We didn't stop there, we introduced the Hybrid logic as well. The result is a patented system whereby a single controller can bring on a condensing boiler first when the water is cold enough to take advantage of the higher efficiency of a condensing boiler. This maximizes system efficiency at the lowest operating cost while maintaining comfort and protecting the non-condensing boilers, and still keeps lead/lag positions straight within each boiler group. Not satisfied with that, we've extended the line further, adding even more functions with plug-in modules.

Basic Data
Model Consists of Total # of Units
B-36 Basic Unit 4
B-37 B-36 plus 6-boiler extension 10
B-38 B-36 plus TWO 6-boiler extensions 16


Features:
  • Supports both condensing and non-condensing units
  • LCD display
  • Programmable lead/lag function
  • Flexible programming
  • System water sensor included
  • Outdoor air sensor included
  • Compatible with all MVBs, all Xtherms, all Xfyres, HiDeltas equipped with the B-60 staged interface board, and Raytherms equipped with the B-35 interface adapter.
 

OPTIONS for the Temp-Tracker Mod+ Hybrid controller:

B-39 4-20 mA Remote Setpoint Module

This interface module provides the Temp-Tracker Mod+ Hybrid controller with the capability of receiving an external 4-20 mA signal as a setpoint override signal. Now your Buiilding management system (BMS) can control the controller. One per controller.
 

B-60 Staged Interface Module

The Hybrid controller uses a 0-10VDC modulating signal to control the firing rate of the units it handles. With this module, that same modulating signal is converted into stage closure, allowing the modulating controller to control Hi Delta staged units. One B-60 board mounts inside the J-box of each Hi Delta.
 

B-62 BACnet MS/TP Interface Module

This module provides full BACnet communications with the Building Management System.
 

Temp-Tracker Mod Digital Controllers

The Temp Tracker Mod controllers are integral to MVBs and XTherms, and available to control a single Raytherm boiler or water heater that uses motorized modulation: H2 sizes 514-4001, or WH2 sizes 2100-4001. On these sizes, it is available factory-mounted only. This control can be used for space heating and hot water supply with 8 applications-specific modes to meet various applications, including outdoor reset for heating applications. It monitors and displays inlet and outlet temperatures on all applications as well as monitoring outdoor ait temperature when an outdoor reset application is utilized.

Basic Data
Model Outdoor Reset Active
B-40 No
B-41 Yes


Features:
  • Up to 4:1 turndown
  • LCD display
  • Boiler inlet and boiler outlet water sensors included
  • System water sensor included
  • Outdoor air sensor included (B-41 only)
  • Low power consumption: 120VAC 60 Hz, 3 VA
  • Outdoor air sensor included (B-23 and B-27 only)
  • Weather-resistant enclosure