A-3 Cupro-Nickel Heat Exchanger Tubes
Replaces the standard copper tubes on H and WH units. Standard on WHP units. Cupro-nickel alloy provides superior resistance to chemical attack and erosion.
|
|
A-10 Pressure Relief Valve, 30 PSIG
Opens to relieve excess pressure in the heat exchanger if the pressure exceeds 30 PSIG.
- Offered on H boilers only, all sizes.
- Shipped loose for field mounting on outlet in sizes 1505-2005. Fittings not provided.
|
|
A-11 Pressure Relief Valve, 45 PSIG
Opens to relieve excess pressure in the heat exchanger if the pressure exceeds 45 PSIG.
- Offered on H boilers only, all sizes.
- Shipped loose for field mounting on outlet in size 2005 only. Fittings not provided.
|
|
A-12 Pressure Relief Valve, 60 PSIG
Opens to relieve excess pressure in the heat exchanger if the pressure exceeds 60 PSIG.
- Standard on all H models.
- Shipped loose.
- Not available on WH or WHP units.
|
|
A-14 Pressure Relief Valve, 75 PSIG
Opens to relieve excess pressure in the heat exchanger if the pressure exceeds 75 PSIG.
- Offered on H boilers only, all sizes.
|
|
A-15 Pressure Relief Valve, 125 PSIG
Opens to relieve excess pressure in the heat exchanger if the pressure exceeds 125 PSIG.
- Available as an option on H boilers only, all sizes.
- Standard on all WH and WHP models.
|
|
A-16 Pressure Relief Valve, 150 PSIG
Opens to relieve excess pressure in the heat exchanger if the pressure exceeds 150 PSIG.
- Offered on H and WH units, all sizes.
- Note: Raypak does not support the use of pressure relief valves with a rating higher than 150 PSIG.
|
|
A-17 Pressure Relief Valve, 150 PSIG, for Unfired Pressure Vessel
Available for the secondary heat exchanger only. Opens to relieve excess pressure in the heat exchanger if the pressure exceeds 150 PSIG.
- Offered on H and WH units, all sizes.
- Note: Raypak does not support the use of pressure relief valves with a rating higher than 150 PSIG. .
|
|
C-6 Ignition Module, Single-Try Lockout
Provided for tight compliance with CSD-1 requirements (see G-1 option). This version of the Hot-Surface Ignition module goes into manual-reset lockout if a single ignition trial for ignition fails.
|
|
E-5 Alarm Bell, 4" dia
Adds an audible alarm bell activated whenever the unit goes into alarm state. Silencing and reset buttons provided.
- Available mounted only.
- Raypak does not recommend the combination of a front-mounted pump, TruSeal and right-hand water on sizes 302B, 402B, or 2002B-2342B.
- Offered for all sizes
|
|
E-14 Contact Status Relay
Provides dry contacts to show whether the unit is actually firing; contacts have continuity when the main valve has been energized.
- Available mounted only
- Offered for all sizes.
|
|
F-10 Low Water Cutoff, Remote Probe
A 24VAC device which checks for the presence of water, confirming that the heat exchanger is water-filled. The F-10 option includes manual reset, test button and indicator light.
- Available as factory-mounted only.
- Offered on all sizes
|
|
G-1 CSD-1 compliance
Meets the requirements of the CSD-1 standard for boiler safety as applied in most jurisdictions. This option adds high and low gas pressure supervision (S-1 and S-2 options). In some areas it may be necessary to add the C-6 option. Please note that the CSD-1 requirements applies ONLY to boilers. Water heaters such as WH models are categorically exempted from CSD-1 requirements; see CSD-1 para CG-130(b).
- If the local inspector still requires CSD-1 compliance on excluded units, contact your sales rep.
- Offered on all sizes
|
|
G-2 CSD-1 with Additional Safety Valve
Originally designed to meet the requirements of the Industrial Risk Insurers (IRI) consortium (no longer in existence), this compliance option is retained for those instances where specific engineers require these added functions. This provides the G-1 package with an additional solenoid valve (M-10) and a normally-open vent valve (M-15).
|
|
G-7 State Code Compliance, New Mexico
G-1 compliance with an added auto-reset high limit. |
|
G-8 State Code Compliance, Washington
- Adds an auto limit.
- Offered for H and WH units, all sizes.
|
|
G-9 State Code Compliance, Kentucky
Includes auto and manual limits with maximum settings of 200F. Select a controller with a MAX setting of 200F.
|
|
G-10 Code Compliance, US Post Office
- Adds high and low gas pressure supervision (S-1 and S-2 options).
- Offered on all sizes.
|
|
G-12 State Code Compliance, California
Meets the requirements of the State of California. Specifics vary with the size and type of unit.
|
|
G-15 CSD-1 Field Upgrade
Adds high and low gas pressure supervision (S-1 and S-2 options) and single-try manual-reset ignition (C-6) option.
|
|
I-1 High Limits, Manual Reset 240F Max and Auto Reset 240F Max
- Offered on H boilers only, all sizes.
- Not available on WH, P or WHP units.
|
|
I-6 High Limit, Auto Reset 180F Max and Manual Reset 200F Max
|
|
I-7 High Limit, Auto Reset 200F Max and Manual Reset 240F Max
- Available for H boilers only.
- Offered on all sizes
|
|
I-8 High Limit, Auto Reset 180F Max and Manual Reset Fixed 200F
|
|
I-11 High Limits, Auto Reset 240F Max and Manual-Reset Fixed 240F
- Available for H boilers only, all sizes.
|
|
I-12 High Limits, Auto Reset 200F Max and Manual Reset 200F Max
|
|
M-1 Motorized Safety Valve
- Adds a motorized safety valve to the unit.
- Offered on all sizes.
|
|
M-10 Solenoid Safety Valve
- Adds a solenoid safety valve to the unit.
- Offered on all sizes.
|
|
M-15 Normally-Open Vent Valve
Adds a valve which is open when de-energized, clearing any buildup of fuel gas if the safety valve does not fully close.
- This option must be ordered with either the M-1 or M-10 options. Included as part of the G-2 option.
- Offered on all sizes.
|
|
S-1 Switch, Low Gas Pressure
Adds a manual-reset safety switch to shut off the unit on a safety fault if the inlet gas pressure drops below setpoint.
|
|
S-2 Switch, High Gas Pressure
Adds a manual-reset safety switch to shut off the unit on a safety fault if the manifold gas pressure rises above setpoint.
|
|
S-3 Switch, Low Water Pressure
Adds a manual-reset switch to shut off the unit off the unit on a safety fault if the water pressure drops below setpoint.
|
|
Z-12 Condensate Neutralizer
The Xtherm is a highly condensing unit, generating a continuous stream of acidic condensate from the secondary heat exchanger. This is too acidic to be simply piped to a sanitary drain in many areas; it must be either neutralized or handled as a toxic waste product. This tube is filled with limestone chips, which chemically neutralize the condensate from the unit enough to allow the resulting liquid to be disposed of down a sanitary drain. The limestone chips must be periodically replaced; the estimated time between changes is in excess of a thousand hours of runtime. Limestone chips for landscaping purposes are readily available and are recommended.
- Use separate neutralizers for the primary condensate drain from the unit, and the condensate drain from the vent.
|
|