1.
Low Voltage Wiring Terminal
Up front and easy to get to. Makes sensor wiring and BMS wiring simple
and clean.
2.
On Board Diagnostic Center
Factory-mounted standard equipment. Gives relevant service feedback as
well as possible solutions to clear the fault. All in plain english, no
cryptic codes to decipher. The control also stores up to 16 fault codes
in its history file for the service technician to review.
3.
TempTracker Mod Controller
Standard equipment on the XTherm. This factorymounted multi-function control
delivers precise loadtracking with selectable mode displays that are easy
to access and read.
4.
Combustion Air Fan
Cast aluminum, non-sparking construction. The state of the art variable
speed fan is controlled by the TempTracker Mod and works in smooth harmony
with the main gas valve.
5.
Dungs Gas Valve
The XTherm uses a state-of-the-art main gas valve manufactured in Germany.
This precision gas valve works in perfect unison with the combustion air
fan. The result is silky smooth light-offs and a 4:1 turn down. |
|
6.
Flow Switch
Monitors water flow and provides safe shut down if water flow drops below
the minimum required.
7.
Vent Pressure Switch
Monitors vent pressure and provides safe shut down if back pressure is
excessive.
8.
Gas Inlet
The XTherm will operate at 100% full rate with gas pressures as low as
4.0"w.c.
9.
Boiler Pump
Sometimes referred to as the primary pump. This pump keeps flow through
the heat exchanger.
10.Water
Outlet
11.Water
Inlet
The XTherm can accept 50°F continuous inlet water temperature.
12.
Cold Water Run Pumps
The XTherm comes factory equipped with a built in Cold Water Run system.
This advanced water control system keeps the inlet water temperature to
the primary heat exchanger above 120°F, regardless of the incoming
water temperature. It constantly self adjusts and regulates the incoming
water flow while still maintaining a constant delta-T in the heat exchanger.
|
|
13.
Flue Outlet
Stainless steel Category IV compatible.
14.
Stainless Steel Secondary Heat Exchanger
Recovers waste heat to boost efficiency into 96%+ range. The XTherm utilizes
a separate high-grade stainless steel heat exchanger. This allows the
corrosive combustion condensate to be collected safely without damaging
the heater. There is a condensate disposal connection on the rear of the
heater. The XTherm is also equipped with a condensate switch that will
sense a blocked condensate drain, which protects the heater.
15.
Vertical Heat Exchanger
Cylindrical, multi-pass heat exchanger captures all radiant energy, eliminating
the need for heavy refractory.
16.
Drain Valve
One of two drain valves located at the bottom of the heat exchanger. A
third drain valve is located on the secondary heat exchanger. This allows
for complete winterizing and drainage of the heater.
17.
Viewing Port
Allows for easy burner inspection.
18.Weather-Proof
Jacket
Heavy gauge galvanized steel with a UV-resistant Polytuf powder coat finish
is impervious to weather and corrosion
|